Engine Ashok Leyland
Naturally Aspirated, Turbocharged, Liquid cooled Diesel Engines
conforming to IS 10001, 10002, BS 5514, ISO 3046. Air Cleaner, Diesel
Filter, Oil Filter, Exhaust Silencer, Instrument Panel with safeties
and tripping for engine faults.
Alternator Kirloskar, Crompton, ELGI, Stamford etc.
220V-1ph AC Upto 30 KVA, 415-3ph AC, 0.8 pf. 50 Hz, Screen Protected
Drip Proof, Self Excited, Self Regulated continuous duty, IP 21
confirming to IS 4722, IS 13364.
Control Panel
Inbuilt Standard control panel 220 V, 1Ph up to 30 kva, 415V, 3ph 0.8
pf. 50 Hz type powder coated panel with necessary Inbuilt gear like
Volt Meter with Selector switch, Ammeter with Selector switch,
Frequency meter, MCB, MCCB, For above 125 KVA DG set KW and KWH meter,
Indicating Lamps, DG ON and OFF etc. Any other items can be provided on
request.
Accessories
Inbuilt fuel tank with Necessary Fittings, Battery with leads etc.
Technical Data
| D G Set
Rating |
3 Phase
Current (in Amps) |
Engine
Model |
Cylinders |
BHP |
Fuel Tank
(in Lits) |
Fuel
Consumption (in Lits) |
Sump
capacity (in Lits) |
Battery |
| KVA |
KW |
| 15 |
12 |
21 |
AL GP G15.E5 |
2 |
21.8 |
65 |
2.70 |
8 |
1*120 |
| 20 |
16 |
28 |
AL GP G20.E4 |
3 |
27.5 |
65 |
3.20 |
8 |
1*120 |
| 25 |
20 |
35 |
AL GP G25 .E4 |
3 |
36 |
65 |
4.32 |
8 |
1*120 |
| 30 |
24 |
42 |
AL GP G30 .E4 |
3 |
42.4 |
75 |
5.09 |
8 |
1*120 |
| 30 |
24 |
42 |
AL GP W04D.E4 |
4 |
43 |
65 |
5.26 |
7.5 |
1*120 |
| 40 |
32 |
56 |
AL GP W04D MK1.E4 |
4 |
53.2 |
75 |
6.26 |
7.5 |
1*120 |
| 55 |
44 |
77 |
AL GP 6.65E4 |
6 |
66.5 |
100 |
8.52 |
11.5 |
2*120 |
| 62.5 |
50 |
87.5 |
AL GP W04CT1.E4 |
4 |
75.5 |
100 |
8.78 |
7.5 |
1*150 |
| 75/82.5 |
60/66 |
105/115 |
AL GP 411TC.E4 |
6 |
93 |
125 |
11.9/13.0 |
11.5 |
2*120 |
| 100 |
80 |
140 |
Al GP 412 TCA.E4 |
6 |
121 |
150 |
14.78 |
11.5 |
2*120 |
| 125 |
100 |
175 |
AL GP 680TC+E4 |
6 |
151 |
200 |
19.35 |
19 |
2*125 |
| 250 |
200 |
350 |
AL GWD 618.42 D |
6 |
302.2 |
350 |
36.5 |
22 |
2*180 |
| 3 ½ Core,
Al Armound Cable |
Exhaust
Pipe Line dia (in mm) |
Weight of
DG set (Approx in Kgs) |
D G Set
Dimentions (approx in mm) |
KLR
Acoustic Dimentions (approx in mm) |
| Length |
Width |
Height |
Length |
Width |
Height |
| 10 |
50 |
775 |
1200 |
820 |
1100 |
2400 |
1150 |
1550
|
| 16 |
50 |
860 |
1300 |
820 |
1120 |
2700 |
1150 |
1550
|
| 16 |
50 |
900 |
1850 |
850 |
1130 |
2700 |
1150 |
1550
|
| 25 |
50 |
950 |
1850 |
850 |
1130 |
2700 |
1150 |
1550
|
| 25 |
50 |
750 |
1700 |
950 |
1150 |
2950 |
1250 |
1650
|
| 25 |
50 |
800 |
1800 |
950 |
1150 |
2950 |
1250 |
1650
|
| 50 |
63 |
1100 |
2000 |
830 |
1300 |
3400 |
1400 |
1750
|
| 50 |
63 |
850 |
1850 |
950 |
1350 |
3250 |
1400 |
1750
|
| 70 |
75 |
1350 |
1950 |
960 |
1450 |
3400 |
1400 |
1850
|
| 95 |
75 |
1650 |
2400 |
1050 |
1450 |
3600 |
1550 |
1850
|
| 150 |
75 |
1750 |
2500 |
1150 |
1550 |
3800 |
1550 |
1850
|
| 400 |
125 |
2400 |
3000 |
1400 |
1800 |
4800 |
1800 |
2050
|
|